Petroleum and gas safety alert no. 81 | 11 April 2018 | Version 1
A licensed gas installer sustained burns to his face, hands and legs from a 'flash over' fire caused by a build-up of LP gas in a plant room.
A licensed gas installer conducted an unsafe purge practice during the commissioning of a LP gas system in a nursing home plant room. The concentration of air/gas mixture released into the room through the unsafe purge method exceeded safe levels. After completing the pipework purge, the installer attempted to ignite the hot water units. This ignited the gas build-up in the plant room resulting in a 'flash-over' fire and injuries to the installer.
Investigations are ongoing and further information may be published as it becomes available. The information in this publication is what is known at the time of writing.
We issue Safety Notices to draw attention to the occurrence of a serious incident, raise awareness of risks, and prompt assessment of your existing controls.
Purging is carried out to avoid the possibility of an explosive air/gas mixture existing or forming in piping, appliances or confined spaces. Purging is required when commissioning or decommissioning a gas system, part of a gas system or a gas appliance. Purging is the displacement of—
(a) air, or an inert gas, by a fuel gas; or
(b) a fuel gas by air, or an inert gas.
Note: Nitrogen is the preferred inert gas.
AS/NZS5601.1 Gas installations Part 1 General installations.
Contact: Paul Beaumont, Principal Inspector (Gas Work) , +61 7 5459 6189 gassafe@dnrme.qld.gov.au