Mines safety alert no. 264 | 18 April 2011 | Version 1
Investigations are ongoing and further information may be published as it becomes available. The information in this publication is what is known at the time of writing.
We issue Safety Notices to draw attention to the occurrence of a serious incident, raise awareness of risks, and prompt assessment of your existing controls.
Testing several units revealed varying backfeed voltages from identical units, as well as backfeed on a unit from another manufacturer. These units were not fitted with protective devices to limit or shutdown supply if a person received a backfeed shock. Another unit showed no backfeed, so did not present a hazard to anyone performing electrical work or simply unplugging smaller plug in units.
All mine types
A recent electric shock at a mine has highlighted the hazard of backfeed on some uninterruptable power supply (UPS ) units. These apparatus provide emergency power to a load when the input mains power is interrupted or disconnected. However, in this case, 240Vac was measured on the plug pins of the disconnected UPS mains supply cable while the UPS was powering a load. Subsequent testing of other units on site revealed 75% of all models and brands tested had backfeed voltages of 55Vac or more.
Various UPS systems.
When the mains supply is isolated, any UPS backfeed voltage could possibly energise otherwise isolated circuits. As this backfeed voltage is unlikely to be covered by any protection circuitry, it could prove lethal to anyone coming into contact with this circuit.
Lack of backfeed protection as required under AS 62040.1.1-2003 Uninterruptible power systems (UPS)—General and safety requirements for UPS used in operator access areas, section 5.1.4 Backfeed protection.
Contact: minesafetyandhealth@dnrm.qld.gov.au
Issued by Queensland Department of Employment, Economic Development and Innovation
Find more safety notices
Search the hazards database
All information on this page (Hazard of backfeed on some UPS units - https://www.rshq.qld.gov.au/safety-and-health-alerts/mines/hazard-of-backfeed-on-some-ups-units) is correct as of time of printing (Nov 15, 2026 7:42 am).