Mines safety bulletin no. 153 | 29 March 2016 | Version 1

Handling and management of surface trailing cables (update to Safety Bulletin 6)

Recommendations

Surface mines using trailing cables should develop, implement and maintain a Trailing Cable Management System, addressing, as a minimum, selection criteria for trailing cables addressing application and intended use, and standards for the operation of trailing cables including:

  1. Regular inspection including in-situ visual inspection by machine operators
  2. Regular testing, maintenance of test records, defining life cycles for each cable application and defining measures to monitor and measure life cycle criteria
  3. Route criteria including support measures where applicable, methods and heights for crossings, identification measures for cables, location of cables in proximity to roadways, protection measures required where it is necessary to swing over the top of cables, construction of adequately sized rock drains and vehicle crossings
  4. Methods for relocating cables and providing adequate equipment for the task, for example cable reelers and relocators
  5. Repairs and testing of trailing cables to AS/NZS 1747 by competent persons, maintaining records of each cable's repair history and defining temporary repair measures and when they can be applied
  6. Defining manual handling methods and providing adequate aids to eliminate manual handling sprains and strains. Also consider equipment to aid in separating and joining plugs. Note that 1 metre of 11kV Type 409 cable weighs about 15 kg, and that manually handling energised trailing cable plugs and receptacles is not accepted practice
  7. Regularly inspecting and performing preventive maintenance on cable accessories such as reeling devices
  8. Regularly inspecting, maintaining and testing electrical protection devices and substation earthing systems, including earth mats, earth impedance, earth connection points, protection relays and trip batteries
  9. Providing unique clear identifiers for each cable and trailing cable plug and substation outlet
  10. Defining when trailing cable protection relays can be reset and re-energised if the relay indicates a fault
  11. Specific regulatory requirements to be met
  12. Inspection and test procedures for equipment including earths and connections, earth impedance, cables, substations and protection equipment after equipment relocation. Additional protection from potential fault touch and step voltages may be achieved by management of protection relay settings (Refer AS/NZS 4871.1)
  13. Review and audit of the cable management system
  14. High voltage switching, access and authorisation systems are developed, implemented monitored and reviewed
  15. Eliminating direct handling of energised cables if practicable, otherwise use insulated lifting equipment, insulated gloves, slings or other suitable equipment
  16. Providing appropriate training in trailing cable hazard awareness for anyone working with them
  17. Designating adequately designed, established and maintained cable laydown areas.

References and further information

1. AS/NZS 1747 - Reeling, trailing and feeder cables used for mining - Repair, testing and fitting of accessories

2. AS/NZS 4871.1 - Electrical equipment for mines and quarries Part 1: General requirements

3. Safety Alert 319 - Dragline and Cable Tractor Interaction (Queensland Mines Inspectorate, Mine Safety and Health)

Introduction

Trailing cables carry large amounts of electrical energy when supplying surface mining equipment, including pontoon pumps, draglines and shovels at voltages from 415V to 22kV.

In 2014 and 2015 the Queensland Mines Inspectorate received ninety reports of damage to high voltage trailing cables supplying draglines (64 incidents) and electric overburden shovels (26 incidents).

Incidents due to rocks falling from buckets and the spoil dumps rose from four in 2014 to ten in 2015 (eight of these occurred at draglines representing 30% of reported dragline cable incidents) – see photos.                       

Incidents of damage due to cable tractors improved from sixteen in 2014 to six in 2015, but this still represents 14% of the cable damage issues in 2015. Also, 2015 saw two very serious cable tractor-dragline interactions; refer Safety Alert No.319 for more information.

High potential incidents involving trailing cables at surface mines include:

This discussion will cover handling, management and general operation of the cables, and seeks to raise awareness of potential hazards from principally high voltage trailing cables at surface mines. It also highlights areas that may need attention to ensure risks are at an acceptable level.

Potential Hazards

Machine operators have a higher potential of injury from trailing cables as they are among those most exposed to the cables while they are energised. Potential hazards from surface trailing cables include: 

Potential Risks

Under normal conditions, risks from an energised trailing cable are low, but this can change through:

Then the risks may become unacceptable! Injury, equipment damage or near hits may result. Incidents, damage or injury are indicators that risks are not being managed as they should!

Depending on where the machine is in its working cycle when cable damage occurs, power tripping may excessively strain mechanical components, for example, if power to the dragline trips while hoisting a full bucket and swinging, excessive strain may be placed on the boom and suspension ropes.

Another potential risk if the trailing cable is damaged while the dragline is in its regenerative cycle, such as plugging and lowering the bucket into the pit, is power may be back-fed into the damaged cable, causing arcing damage which continues for some time despite the electrical protection relays operating correctly and tripping the supply.

Typical surface trailing cable construction

Typical trailing cables have a durable, hard-wearing sheath designed to separate the power conductors from the external environment and allow the cable to operate and withstand mining conditions.

Generally an earthed barrier is located between insulated power conductors so if damaged a fault to earth (phase to earth) likely occurs before a larger power conductor to power conductor (phase to phase) fault. Earth fault current limitation devices are installed for all high voltage trailing cable installations.

Typical trailing cables also contain a small pilot wire, typically at the centre of the cable, used with protection relays to trip power in the event of cable breakage or plug separation, or prevent power up if plugs are separated or the cable is broken (pilot wire broken). Note: care must be taken with asymmetrical designs, having a pilot wire in the interstices of the trailing cable, to ensure capacitive and inductive coupling does not have the potential to reduce the reliability of protection relays.

Typical sources of cable damage

Typical sources of cable damage include:

Authorised by Russell Albury - Chief Inspector of Coal Mines

Contact: Neville Atkinson, Inspector of Mines , +61 7 49360130

Issued by Queensland Department of Natural Resources and Mines

Placement: Place this announcement on noticeboards and ensure all relevant people in your organisation receive a copy.

All information on this page (Handling and management of surface trailing cables (update to Safety Bulletin 6) - https://www.rshq.qld.gov.au/safety-and-health-alerts/mines/handling-and-management-of-surface-trailing-cables-update-to-safety-bulletin-6) is correct as of time of printing (Oct 31, 2026 4:13 am).