Mines safety alert no. 43 | 12 January 2001 | Version 1
Investigations are ongoing and further information may be published as it becomes available. The information in this publication is what is known at the time of writing.
We issue Safety Notices to draw attention to the occurrence of a serious incident, raise awareness of risks, and prompt assessment of your existing controls.
All underground mines
Fortunately no injuries occurred when underground mine employees were exposed to non-insulated energised power conductors in an underground mine.
A pulsating fire resistant anti static (FRAS) pump discharge line wore through the mining cable insulation and sheath to expose bare copper conductors.
Type 275 mining trailing cable, dewatering pump and 1000V electrical power supply
Should anyone have touched the exposed conductor they would have received an electric shock which could have proved fatal.
A type 275 mining cable utilising conductive rubber screening (eg shuttle car cable) was being used to power a dewatering pump in an underground coal mine. The short circuit, earth leakage and earth continuity circuit protection did not recognise the hazard as there was no circuit to earth due to both cable and hose being non-conductive. Protection settings for pump stations and like installations do not offer personal protection from electric shock. Lack of potential hazard awareness during installation of the pump station and inadequate subsequent inspection activities.
The site recognised Standard for Cable Management is to be reviewed to ensure known and identified hazards such as wear and abrasion are managed in an appropriate manner.
Cables must be protected against physical damage and an appropriate management/ inspection system must be introduced to monitor cable condition.
Contact: minesafetyandhealth@dnrm.qld.gov.au
Issued by Queensland Department of Natural Resources and Mines
Find more safety notices
Search the hazards database
All information on this page (Exposed live conductors underground - https://www.rshq.qld.gov.au/safety-and-health-alerts/mines/exposed-live-conductors-underground) is correct as of time of printing (Nov 12, 2026 2:00 pm).