| Mines safety alert | No.231 V 1 | 21 October 2009
All mine types
Recently at a coal handling and preparation plant, the coal stacker was electrically isolated to allow for maintenance work. On completion of the work, attempts to re-power the stacker failed. The electrical switching mechanism from a ring main unit (RMU) had failed, and the mechanism needed to be removed for evaluation and/or replacement.
A switching mechanism from a spare RMU was also to be removed for use as a possible replacement. This 22,000v RMU can be seen below, with the 3-phase high voltage bushings shown in the lower half of the picture. The switching mechanism has been removed from in front of the hexagonal-shaped operating shaft in the middle top right of the picture. A vertically moving truck located behind this panel connects these three bushings to live, off, and off and earthed positions, depending on where the operating shaft is positioned. With the truck at the topmost position, the three bushings are disconnected from power and earthed. In the middle position, they are disconnected from power, while in the lowest position, they will be contacting the live 22,000v conductors.
When the electrical switching mechanism was removed from this unit, it was de-energised by moving the switching mechanism to the off position, which was then locked in place. However the hexagonal operating shaft was not locked in position and was only held in place by the switching mechanism. The switching mechanism was then removed. As the two electricians were replacing the external covers an arc flash occurred, causing serious burns to both electricians' hands.
High energy arc flash.
RM6 ring main unit.
The exact cause of the incident is still under investigation. At this stage, it appears that the high voltage bushings on the RMU were re-energised as the operating shaft rotated and the truck mechanism in the RMU moved under gravity from the off to the live position.
As the electricians were re-assembling the cabinet, it appears an arc flash was initiated by clothing coming in contact with the high voltage terminal, initially creating a phase to phase short circuit.
Contact: minesafetyandhealth@dnrm.qld.gov.au
Issued by Queensland Department of Employment, Economic Development and Innovation
Find more Safety and Health Alerts
Search the hazards database
All information on this page (Arc flash injuries received from 22kV ring main unit - https://www.rshq.qld.gov.au/safety-and-health-alerts/mines/arc-flash-injuries) is correct as of time of printing (Nov 16, 2026 2:24 pm).