Alert no. 107 | 11 November 2022 | Version 1
Recent instances of corroded electrical components have resulted in a fire on a Mobile Processing Unit (MPU) and a no-flow condition of an ammonium nitrate emulsion (ANE) pump.
Damaged electrical components in the vicinity of ammonium nitrate product were subject to corrosion. Routine maintenance and pre-start inspections failed to identify and replace affected wiring, solenoids, actuators and switches.
In one instance, a wiring harness with damaged insulation on a MPU bin lid actuator energized resulting in a small fire.
In another incident, an internally corroded actuator energized and started a NAPCO™ ANE pump while the mine re-load was unattended.
Critical hazards associated with ammonium nitrate and ANE that affect electrical components include:
Where ANE pumps are inadvertently activated, or where ANE pumps fail to shut down, no-flow events introduce heat into the ammonium nitrate emulsion, generally under confinement. This can lead to thermal decomposition of ammonium nitrate emulsion and an unplanned detonation event.5
Contact: Haydn Isaac, Principal Inspector of Explosives – Northern Operations , +61 7 3199 8023 explosives@rshq.qld.gov.au
Issued by Resources Safety & Health Queensland
Find more safety notices
Search the hazards database
All information on this page (Electrical component failure on ammonium nitrate handling and transfer equipment - https://www.rshq.qld.gov.au/safety-and-health-alerts/explosives/electrical-component-failure-on-ammonium-nitrate-handling-and-transfer-equipment) is correct as of time of printing (Nov 5, 2026 11:38 pm).